Product details

The combined transformer (another name is metering tank) is one kind of outdoor power measuring instrument , which is composed of two sets single-phase wholly insulated voltage transformers, forming three-phase V/V wiring, and two current transformers are separately series connected to A and C phase.
The JLS-6, 10, metering tank is one upgraded product based on old product of same kind, just adding moisture-proof device onto oil tank's cover, which could effectively prevent external humidity from entering into oil, so as to prolong service life of product, while, compared with old product, its advantage contains larger capacity, smaller volume and weight, simplifying installing.
This product is applied to certain outdoor circuit of AC50-60Hz, rated volt being 35kV or lower, to be used for metering of current, voltage and electric energy etc. this product is suitable for rural outdoor transformer substation, miniature transformer station and substation of industrial enterprise etc. Adding active and reactive energy meter onto combined transformer is named as high volt power metering tank.
10kv high voltage ct-pt measuring units combined Instrument transformer 
Technical data
Metering tank conforms to given provisions in GB17201-2006 <combined transformer>;
Current transformer conforms to given provisions in GB1208-2006 and IEC 660044-1;
Voltage transformer conforms to given provisions in GB1207-2006 and IEC 60044-2 ;
The zinc oxide arrester must be installed at certain position with less-than-one meter distance away from product's installation place, for lightning protection.
 
JLS-10 Voltage transformer technical data
Type Rated primary voltage(kV) Rated secondary voltage(V) Maximum voltage(kV) Accurate level and output capacity COSφ=0.8(lag)(VA)  Maximum output capacity (VA)
0.2 0.5
JLS-10 10 100 12 20 50 640

JLS-10 Current transformer technical data
Rated primary voltage(kV) Rated secondary voltage(V)
 
Accurate level and output capacity COSφ=0.8(lag)(VA) 1S Shorttime thermal current Rated peak withstand current
 
10 100 15-100 0.2S 600I1n 150I1n
5 10